Test 11R
11_Retest_8x9-ledger-osb-54mil-8’up
(stud: 600S162-54mil(33ksi))
Everything looks good.
We use 600S162-54mil(33ksi) as our field studs and chord studs.
Strap is good, no gap.
After test
Peak load:8708.3lbs
Displacement: 2.4182in.
Failure occur at vertical seam and OSB bottom, fasteners titled then pull through.
Failure is at one of 4x8 OSB on south side.
Fasteners at vertical seam on south side complete pull through,
3 fasteners at horizontal seam near vertical pull through
3 fasteners at the bottom near vertical seam pull through.
At the edge of  horizontal seam, OSB tear out.
Fasteners on south side field stud title, no damage.
Observe all the fasteners at the strap and bottom title.
Photo
 After test
 horizontal seam and vertical seam
 After test 
 Middle field stud
 Bottom of vertical seam
 Fasteners at the strap
Fasteners at middle field stud