Tuesday, December 6

Ninth week

From Peng
To file
12/6/2011
Test13
13-8’x9’-ledger-OSB-GYP-8’up seam
Pretest
Put the shear wall in the test frame first, then put the gypsum board on it, clap them, drill screws and cut half inch at the bottom. Look good.
Check the OSB side, one fastener at vertical bottom close to the OSB edge.
Other fasteners are okay.
Photo 



Meanwhile, we are doing the fasteners and OSB(horizontal and vertical strand) connection test.




Ninth week

From Peng
To file
12/6/2011
Test12
12-8x9-ledger-OSB-54mil-8’up seam cyclic
Pretest
43circles
Reference displacement:2.92x0.6in.
8’x9’ shear wall, horizontal seam at 8’up.Vertical seam at 4’over.
Strap is good.
2 over-drilling screws at the horizontal seam recorded
Anchor spacing is 2’

After test
Peak load+:10049lbs
Displacement: 2.2672in.
Peak load-:-8443.1lbs
Displacement:  -1.6616in.
The failure occur at the bottom, fastener pull through OSB with titled
Fasteners up to 2’high on the chord studs pull through the OSB
At the bottom vertical seam which is up to 1’, the fasteners fail with wood bearing failure and pulling through OSB.
The strap is good, no damage observed
The outside of the horizontal seam tear out.
The connection of the vertical and horizontal seam is broke because of the contact.
Fasteners in the corner at the bottom are cut off the head.
Photo

 After test
Bottom fasteners (1)
 Bottom fasteners (2)
 Bottom fasteners (3)
 Bottom fasteners (4)
 Bottom 


Ninth week

From Peng
To file
11/30/2011
Test 11R
11_Retest_8x9-ledger-osb-54mil-8’up
(stud: 600S162-54mil(33ksi))
Everything looks good.
We use 600S162-54mil(33ksi) as our field studs and chord studs.
Strap is good, no gap.
After test
Peak load:8708.3lbs
Displacement: 2.4182in.
Failure occur at vertical seam and OSB bottom, fasteners titled then pull through.
Failure is at one of 4x8 OSB on south side.
Fasteners at vertical seam on south side complete pull through,
3 fasteners at horizontal seam near vertical pull through
3 fasteners at the bottom near vertical seam pull through.
At the edge of  horizontal seam, OSB tear out.
Fasteners on south side field stud title, no damage.
Observe all the fasteners at the strap and bottom title.
Photo
 After test
 horizontal seam and vertical seam
 After test 
 Middle field stud
 Bottom of vertical seam
 Fasteners at the strap
Fasteners at middle field stud

Thursday, December 1

Eighth week

Assemble another 8'x9'shear wall today.
Double check the details.
Will do monotonic test with Dr.Yu tomorrow afternoon.
Photo